Project Description
Shut-off , poppet valve ZB
- 2/2 cl.A
- opened only manually (pulling the handle), closed with electrical impulse coming from gas detection system, which detect dangerous gas concentration
- valve might be closed also manually (with button)
- permanent strainer built-in
- adapted for external applications
- conforms to PN-EN161
- in Gas Safety Systems of: gas boiler rooms, domestic installations – as an actuator that surely and effectively cuts off the gas supply to installations
- in low pressure gas installations
- additionally valve can be used as manual stopcock,
fluid media | gas fuels | |
pressure | See tab „Dimensions / Pressures” | |
fluid media temperature | -25°C ÷ +60°C | |
ambient temperature | -25°C ÷ +60°C | |
trigger type electrical impulse Min. impulse time duration power operation type |
WE DC 12V ti > 0,2s 26W continuous |
EZB-12,6G AC(50Hz) 230V ti > 0,3s 45VA continuous |
opening | manual | |
closing | electrical impulse or manually – with button | |
closing time | < 1s | |
degree of protection | IP54 | |
valve body material | aluminium alloy | |
sealing material | nitrile-butadiene rubber NBR | |
mounting position | arbitrary |
Typ | Dn | Rp | A [mm] |
B [mm] |
E* [mm] |
L [mm] |
PMAX [bar] |
ΔP [bar] |
M [kg] |
---|---|---|---|---|---|---|---|---|---|
Threaded connection | |||||||||
ZB-20 | 20 | 3/4 | 135 | 22 | 77 | 105 | 0,25 | 1,0 | 1,20 |
ZB-25 | 25 | 1 | 145 | 28 | 80 | 115 | 0,25 | 1,0 | 1,35 |
ZB-32 | 32 | 1 1/4 | 155 | 37 | 101 | 145 | 0,25 | 1,0 | 1,96 |
ZB-40 | 40 | 1 1/2 | 180 | 43 | 110 | 180 | 0,25 | 1,0 | 2,62 |
ZB-50 | 50 | 2 | 188 | 41 | 140 | 193 | 0,25 | 1,0 | 3,18 |
ZB-65 | 65 | 2 1/2 | 222 | 61 | 170 | 240 | 0,25 | 1,0 | 4,81 |
Flanged connection: | |||||||||
ZB-50k | 50 | 215 | 78 | 165 | 230 | 0,25 | 1,0 | 7,40 | |
ZB-65k | 65 | 240 | 83 | 182 | 270 | 0,25 | 1,0 | 17,15 | |
ZB-80k | 80 | 313 | 94 | 200 | 310 | 0,25 | 1,0 | 23,65 | |
ZB-100k | 100 | 325 | 103 | 220 | 350 | 0,25 | 1,0 | 27,10 |
- in both open and closed positions valves do not require power supply – they are energy efficient (electrical impulse with duration <1s is needed only to close the valve)
- insensitive to voltage decay supplying the system – its absence or temporary decay does not cause changes in the gas flow through the valve
- resistant to any interferences that in the closed state can cause accidental valve opening (only conscious actions of supervisors)
- very small maneuvering area required to operate and small force needed to open the valve
- simple, cheap, reliable and lightweight construction
- long lifespan